The Hager BD163T is an earth leakage add-on block that provides residual current protection for three phase circuits. It fits alongside a compatible three pole miniature circuit breaker within a distribution board and adds earth leakage detection to the existing overcurrent protection. The unit is one module wide and mounts on standard DIN rail, with screw terminal connections for the three phase conductors and neutral.
This block is rated at 63A with a rated residual operating current of 30mA and is a Type A device, which responds to alternating and pulsating direct residual currents. It carries a test button to allow periodic verification of the tripping function. This listing is for a single spare unit held in stored stock and is offered for maintenance and replacement use.
Specifications
Brand: Hager
Model: BD163T
Part Number: BD163T
Product Type: Earth Leakage / RCD Add-On Block
Poles: 3 pole (neutral on right)
Rated Current: 63 A
Rated Residual Operating Current: 30 mA
RCD Type: A
Module Width: 1 module
Rated Voltage: 240 to 415 V
Rated Insulation Voltage: 500 V
Impulse Withstand Voltage: 4 kV
Frequency: 50 Hz
Connection: Screw terminals
Mounting: DIN rail
Dimensions: 121 x 70.8 x 69.1 mm
Condition: Spares Stock (new old stock)
Key Features
- Adds residual current earth leakage protection to a compatible three pole MCB
- Type A detection of alternating and pulsating direct residual currents
- 30 mA rated residual operating current
- One module wide format
- DIN rail mounting with screw terminals
- Integrated test button
Typical Applications
- Three phase distribution boards
- Circuits requiring added earth leakage protection
- Commercial and industrial installations
Package Includes
- One Hager BD163T earth leakage add-on block
- Does not include an MCB, DIN rail, or additional mounting hardware
Additional Information
Specifications listed are drawn from the manufacturer datasheet. Verify suitability and compatibility with the intended MCB and installation before use. Installation must be carried out by a licensed electrician in accordance with local wiring regulations.
The item is new old stock and the packaging may show minor shelf wear from storage.